Sizing by capacity at your design temperature

How big a mini-split do you need in the cold?

The short answer

Size from your heat loss at your 99% design temperature, not from the 47°F label. To cover a 24,000 BTU/h load, a unit shaped like the median certified system needs about 24,000 BTU/h of 47°F rating in Miami (56°F design) but 30,860 BTU/h in Fairbanks (-33°F), because the median unit keeps only 88% of its capacity at 5°F.

The median unit's capacity curve

012,50025,000 18,0005°F16,50017°F20,00047°F Outdoor temperature · y-axis: BTU/h heating capacity
Solid dots: 5°F and 47°F medians, joined by the straight line our model uses. Open dot: the 17°F median as reported, which is a separate test condition and often falls below the 5°F maximum-capacity figure.

Required 47°F rating, by climate

Ten cities from warmest to coldest of our 121. Same 24,000 BTU/h design load everywhere, so the only thing changing is the cold.

47°F rating needed to cover a 24,000 BTU/h load at the design temperature
City99% design tempNeeded 47°F rating (BTU/h)Certified systems that cover the load
Fairbanks, AK-33°F30,8604,119 of 14,941
Bozeman, MT-6°F28,1454,628 of 14,941
Des Moines, IA0°F27,6055,075 of 14,941
Milwaukee, WI4°F27,2655,303 of 14,941
Toledo, OH7°F26,9675,436 of 14,941
Manchester, NH9°F26,8335,436 of 14,941
Wichita, KS13°F26,5125,544 of 14,941
Santa Fe, NM16°F26,2625,550 of 14,941
Salt Lake City, UT20°F25,9545,599 of 14,941
Huntsville, AL25°F25,5635,627 of 14,941
Shreveport, LA30°F25,1905,688 of 14,941
Jacksonville, FL36°F24,7575,940 of 14,941
Miami, FL56°F24,0006,996 of 14,941

Method: capacity between 5°F and 47°F is a straight line through the two ENERGY STAR test points; above 47°F it is flat; below 5°F it never rises. The 17°F value is plotted as reported but not used, because ENERGY STAR reports it under a different test condition (in the data it is below the 5°F figure for 52% of systems). The curve's 17°F point is the median 47°F capacity times the median 17°F-to-47°F ratio.

Questions people ask

Why not size a mini-split by square feet?

Heat loss depends on insulation, windows and air leakage, not floor area. Size from a Manual J load calculation at your 99% design temperature, then check the unit's published capacity at that temperature.

Is bigger better in cold climates?

Not automatically. Oversizing mostly adds cost and cycling. The right question is whether capacity at your design temperature meets the load, and that is what the table below computes.

What if my design temperature is below 5°F?

ENERGY STAR certifies capacity down to 5°F only. Below that, check the manufacturer's published low-ambient capacity and plan backup heat; our model never lets capacity rise below 5°F.